8. Lift the protective cover from the Power Entry module.
The fuses are mounted vertically under the cover.
Use a small flat blade screwdriver and lift the fuses
from the clips.
9. Replace the fuses with the specified current rating and
voltage.
10. Replace the Power Entry module cover. Insert and
tighten the cover screw. Lower and align the heatsink
bracket and tighten the two screws with a screwdriver.
Check for proper alignment of the auxiliary Foot
Control cable connector on the back panel and that
no wires are trapped.
11. Install and tighten the two screws at the rear corners
of the Power Supply assembly.
12. Align the plastic barrier with the Bottom Housing and
fully seat. Replace the two-sided tape, if necessary, to
secure the barrier to the heatsink.
13. Reconnect the ribbon cable from the Top Cover.
Support the Top Cover on the rear of the base cabinet.
14. Align the Top Cover on the Bottom Housing and
securely fasten the six #6 x 1/2” Hi-Lo screws using a
screwdriver.
15. Plug in the power cord into the power entry module.
16. Power up the unit using the power rocker switch and
test unit operation.
17. Calibrate and final test the Cavitron
®
Plus™ Scaler
using the DENTSLY
®
Professional - Product Service
Standard Operating Procedure, PS-153.


1. If possible, plug the water supply hose into a
compressed air source (40 psi max.) and operate the
unit to discharge all water from the unit and handpiece.
2. Follow the steps above in Section A for “Top Cover
Removal”.
3. Unplug the Top Cover ribbon cable at J5 on the Power
Drive PC board and place the Top Cover to the side.
4. Remove the plastic barrier from the unit. Pull the
barrier away from the heatsink to release the two-
sided tape and lift the barrier out of the unit.
5. Unplug the 3-wire Handpiece cable from J3 on the
Power Drive PC board.
6. Carefully slide the Handpiece water tubing from the
Regulator/Water Solenoid assembly.
7. Apply slight pressure upward on the Handpiece cable
strain relief. At the same time, separate the plastic
clips and fully disengage the handpiece strain relief
and cable from the cabinet base.
8. Pass the wiring and water tubing through the Bottom
Housing opening.
9. Insert the new handpiece wire connector and water
tubing through the bottom of the cabinet base. Align
and snap the strain relief into the tabs.
10. Plug the 3-wire connector onto J3 of the Power PC
board. Route the Handpiece cable down against the
chassis.
11. Align the plastic barrier with the Bottom Housing and
fully seat. Replace the two-sided tape, if necessary, to
secure the barrier to the heatsink.
12. Route the handpiece water tubing by first creating a
counter-clockwise loop above the strain relief. Then
route the tubing along the chassis and connect it to
the water regulator/solenoid.
13. Reconnect the ribbon cable at J5 on the Power PC
Drive board. Support the Top cover to prevent
damage to cable.
14. Power up the unit, install an insert in the handpiece,
and check the scaling power and water flow. Inspect
the clear handpiece water tubing for any water leaks.
15. Calibrate and final test the Cavitron
®
Plus™ Scaler
using DENTSPLY
®
Professional - Product Service
Standard Operating Procedure, PS-153.

1. Follow the steps in Section A for “Top Cover Removal”.
2. Unplug the Top Cover ribbon cable at J5 on the Power
Drive PC board and place the Top Cover to the side.
3. Remove the plastic barrier from the unit. Pull the
barrier away from the heatsink to release the two-sided
tape and lift the barrier out of the unit.
4. Locate the BLK-WHT wire harness that is connected
to the power switch and unplug it from the Power
Supply assembly.
5. Unplug the Ground Lug at the front-right corner of the
Power Supply assembly.
6. Unplug the BLK-RED wire connector at J1 on the Power
Drive PC board.
7. Use a screwdriver and remove the two #6 x 1/2” Hi-Lo
screws at the back corners of the Power Supply
assembly.
8. Lift and slide the Power Supply assembly toward the
rear of the unit to disengage it from the front mounted
tabs and remove.
9. Inspect the cabinet base for the presence of the two
D-section support cushions. Replace if damaged or
missing.

HP
Water Regulator/Solenoid
J3
J2